  Description - 7011 Air Purged Flame Detector

The Type 7011 flame detector comprises an outer housing within which is located an inner polycarbonate enclosure. The outer housing is connected to an air blower such as to keep a positive air pressure around the inner unit's sensor windows. A pressure switch signals a fault on air failure.
An adjustable bracket permits alignment in both vertical and horizontal planes. The inner module's fascia and back-box have a high level of ingress protection and are rated at IP66.
Removal of both outer lid and inner fascia provides access to terminals and maintenance features. Cable connection is at plug-in (two part) screw terminals, permitting PCB module removal without wiring disconnection.
The unit has open collector transistor type outputs which may be directly used for fire and fault signaling in "Low Power Mode". Alternatively "Relay Mode" may be selected which provides volt free change over contacts.
Sixteen LEDs provide indication of the dynamic status of the eight flame detection channels. These are principally used as commissioning and maintenance aids. During normal operation, in order to minimize supply current, the indicators are usually disabled by means of PCB jumpers.
Located at the rear of the fascia unit is a six pole SIL program switch for setting the sensitivity level and optical axis focal ‘zoom’ characteristics of the device.

Specification
Supply Voltage:-   Detectors:-
Relays Enabled: 20 - 30Vdc   Band Pass : 4.2 to 4.7 um - 8 off
Relays Disabled: 13 - 30Vdc   Long Pass 5.0 to 15 um - 8 off
Supply Current:-   Maximum Range:-
Relays Enabled: <30mA Stand By #   Greater than 100m
Relays Disabled: <20mA #
  Angle of View:-
# Maintenance LEDs Disabled
  +/- 45 Degrees from axis
Max / Full Alarm: 50 mA ##   Internal Indications:-
## Relays and LEDs Enabled
  Flame: Red LEDs - 8 off
Enclosure:-   Ambient: Yellow LEDs - 8 off
Material: Polycarbonate  Maintenance Controls:-
Size: 289x239x114 mm (Ex Bracket)   Reset Push-button
Colour: Grey RAL 7032   Program SIL Switch - Range / Zoom
Ingress Protection Rating: IP66   Timer Period - Two bit jumper
Temperature:-   Internal LED Enable Jumpers
-20 to +70 Degrees Centigrade   Relay Mode (Option):-
Weight:-   Alarm Contact : 1 Pole C/O
<2.6 kg - (including bracket)   Fault Contact : 1 Pole C/O
Termination:-   Low Power Mode (Option):-
Two Part Screwed Rising Clamp   Alarm O/P: Open collector norm. off
Max wire size: 4.0 sq mm   Fault O/P: Open collector norm. on
     
Special Options
The flame detector can be fitted with a screened flexible cable connecting to a seperate junction box. In addition to containing connection terminals, this JB unit can be provided with daylight visible LED indicators illuminating on Fire and/or Fault conditions.
 